Symptom |
Possible Cause |
Corrective Action |
Alarm 120 Low Air Pressure Or Flow |
The compressed air supplied to the machine is below the minimum pressure or flow required. |
Check for contamination in air pressure sensor. If contamination is found, sensor must be replaced.
Important: Ensure that air supply to the machine is clean and dry to avoid repeat failures.
|
Alarm 9916 EXCESSIVE THERMAL COMPENSATION DISTANCE |
There is electrical noise on the signal or the thermal sensor is faulty. |
Check the thermal sensor input in diagnostics and see if the signal is fluctuating. If signal is fluctuating, inspect the amplifiers and make sure there is a ferrite bead on ALL axis power cables. Check for loose connection or damage to the thermal sensor cable. If all checks have been done the thermal sensor is faulty. |
Alarm 9940 AXIS THERMAL SENSOR FAULT |
There is electrical noise on the signal or the thermal sensor is faulty. |
Check the thermal sensor input in diagnostics and see if the signal is fluctuating. If signal is fluctuating, inspect the amplifiers and make sure there is a ferrite bead on ALL axis power cables. Check for loose connection or damage to the thermal sensor cable. If all checks have been done the thermal sensor is faulty. |
The cable or sensor is disconnected. |
Check for loose connection or damage to the thermal sensor cable. |
At Power On:
Alarm 4.9940 AXIS THERMAL SENSOR FAULT
Is generated.
|
The I/O Main Firmware is outdated. |
Make sure the I/O Main Firmware is version 4.09 or higher. Refer to the I/O Firmware Upgrade procedure. |
After software update machine generates
Alarm 4.9916 / 9916 EXCESSIVE THERMAL COMPENSATION DISTANCE
OR
4.9940 / 9940 AXIS THERMAL SENSOR FAULT
|
Invalid I/O configuration files. |
Make sure that the thermal sensor is mapped to the correct I/O analog input. |
This applies to UMC machines: Axis thermal sensor cable is plugged into the wrong analog input. |
Make sure the axis thermal sensor cable is plugged into P45 on the I/O PCB. |
There is electrical noise on the signal or the thermal sensor is faulty. |
Check the thermal sensor input in diagnostics and see if the signal is fluctuating. If signal is fluctuating, inspect the amplifiers and make sure there is a ferrite bead on ALL axis power cables. Check for loose connection or damage to the thermal sensor cable. If all checks have been done the thermal sensor is faulty. |
ALARM 9941 CRASH DETECTED (spindle head accelerometer) |
The machine detected a crash |
Verify the program machine movements to make sure the machine does not crash |
The Accelerometer unit, cable or spindle head CAN board is damaged |
- Verify analog inputs are not 0 (cable unplugged)
- I/O board minimum version 4.09 (update to latest if possible)
- Spindle head CAN board minimum 1.10 (update to latest if possible
- Make sure to take an error report (SHIFT+F3), error reports will have information about the crash direction and magnitude in the JavaConsoleLog.txt file (refer to Crash Detection Section in the Accelerometer Troubleshooting Guide for further information)
|
ALARM 966 EXCESSIVE TOOL IMBALANCE (board accelerometer) |
Excessive tool vibration is generated by on board accelerometer |
Verify that everything is properly balanced, such as tools and spindles |
Reduce sensitivity using Setting 245
- Setting 245 = Normal: Means that parameter 856 is directly used
- Setting 245 = Low: Means that parameter 856 is multiplied by 1.5
- Setting 245 = Off: Alarm 966 will not be thrown.
NOTE: Setting 245 will not persist when the power is cycled
Please refer to the Accelerometer Troubleshooting Guide for further information
|
Spindle motor temperature sensor fluctuating |
Electrical noise around that area. |
A ground wire should added from the motor lift bracket to the spindle heat shield. Refer to: HSG-N 08-23-2024. |